Modbus TCP / EtherNet/IP to PROFINET Gateway
GT200-PN-MT
909-977-2988
WhatsApp
WhatsApp
+1-909-977-2988

The GT200-PN-MT gateway enables seamless connectivity between EtherNet/IP scanner/adapters or Modbus TCP devices or and PROFINET networks. It supports MRP ring redundancy and system redundancy (S2). It requires no changes to your existing devices, making integration simple and hassle-free.
-
Technical Specification
-
Order Information
-
Download
-
Quick Start Guide
-
Selection Guide
-
Case Study
-
Related Products
-
Warranty & Service
Network Interfaces
- Equipped with four Ethernet ports: two for Modbus TCP or EtherNet/IP and two for PROFINET, supporting independent IP address configuration for each network segment.
PROFINET Features
- Supports standard PROFINET RT and IRT protocols.
- Supports PROFINET MRP (Media Redundancy Protocol) for ring network redundancy and SR System Redundancy (S2).
- Supports up to 32 slots on the PROFINET side, with a maximum of 1440 input bytes and 1440 output bytes (actual usable length depends on PLC and PDU size of the communication module).
- Input/output byte lengths can be configured via TIA Portal or STEP 7.
EtherNet/IP Features
- Supports ODVA-compliant EtherNet/IP communication protocol.
- Acts as an EtherNet/IP scanner or adapter device.
- Supports I/O and MSG communication mode.
- Maximum output and input data: 1428 bytes.
EtherNet/IP Scanner Features
- Supports connecting up to 64 EtherNet/IP adapters.
- I/O mode supports large data mode.
EtherNet/IP Adapter Features
- Supports Non-DLR (Device Level Ring) operation.
- Supports QoS (Quality of Service).
- SVendor Code is configurable.
Modbus TCP Features
- Supports byte swapping options: No swap, 2-byte swap, 4-byte swap.
- Supports custom server port number; default port is 502.
Modbus TCP Client Features
- Connects to up to 72 Modbus TCP servers.
- Supported function codes: 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x0F, 0x10, 0x17.
- Supports up to 300 Modbus commands.
- Command output modes: Cyclic, Disabled, Change-of-Value, and Control Word Trigger.
Modbus TCP Server Features
- Handles up to 72 TCP client connections.
- Supported function codes: 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x0F, 0x10, 0x17.
General
- Power supply: 24VDC (range: 9–30VDC), 250mA @ 24VDC.
- Power interface isolation: 1.5kV.
- Operating temperature: -40°C to 70°C (-40°F to 158°F).
- Relative humidity: 5%–95%, non-condensing.
Physical Features
- Dimensions (W × H × D): 1.3 in × 4.6 in × 4.1 in (34 mm × 116 mm × 105 mm).
- Mounting: 35 mm DIN rail.
- Protection rating: IP20.